High Efficiency Vertical (1 to 6 tons)

A-Vintage, floor-mounted water source heat pumps are typically installed in closets or small mechanical rooms near the occupied space.  Each unit provides heating and cooling to a specific space within the building.  A-Vintage units offer you the ability to achieve industry-leading energy efficiency in boiler/tower and geothermal applications. You can benefit from lower energy bills, higher energy rebates (where applicable) and A-Vintage units can help you earn points toward LEED® certification. 


Basic Features and Benefits:

  • Ten units from 1 to 6 tons
  • Standard or geothermal operation
  • R-410A refrigerant
  • EER up to 20.6 and COP up to 5.5
  • ETL listed and AHRI/ISO 13256-1 certified for capacity and efficiency
  • Fully run-tested with water in both heating and cooling modes
  • Three speed PSC motor, size 012, and electronically commutated motor (ECM), sizes 015 and larger, optimize efficiency throughout the unit operating range
  • Two-stage scroll compressor, sizes 024 to 072, optimizes efficiency throughout the operating range of the unit
  • HP-5 microprocessor-based control system including condensate overflow protection
  • Optional EPiC™ DDC controls provide for optimum performance using the control scheme or building management system and protocol of your choice
  • Heavy gauge steel cabinet maximizes durability and unit integrity while minimizing sound and vibration
  • Cabinet insulation provides superior thermal performance and reduces sound
  • Optional sound package for sensitive acoustic applications
  • Available with left or right hand water connections to match application requirements
  • Ample service access through removable panels simplifies and encourages regular maintenance and service
  • Manufactured in the U.S.A. at our Holland, Michigan facility 

For more information, contact your local representative.

ISO 13256-1 Performance Data - Water Loop (Boiler Tower)

Unit Size

CFM 

GPM 

A-Vintage Vertical - Water Loop (Boiler/Tower)1

Cooling

Heating

Qt 

Qs 

kW

EER 

Qt 

kW

COP 

012VHA

400

3.5

13,100

8,900

0.8

15.7

14,300

0.9

4.5

015VHA

520

4.5

16,500

12,200

0.9

18.5

17,000

0.9

5.5

018VHA

600

5.0

21,500

15,600

1.2

18.1

21,800

1.2

5.3

024VHA

800

6.5

28,400

21,000

1.6

18.0

29,200

1.7

5.2

030VHA

1000

9.0

34,400

25,200

2.0

17.1

38,500

2.2

5.2

036VHA

1200

10.5

40,000

30,000

2.4

17.0

40,800

2.4

5.0

042VHA

1400

12.0

44,600

37,400

2.9

15.0

49,000

3.1

4.6

048VHA

1600

14.0

55,500

41,600

2.9

19.0

58,500

3.4

5.1

060VHA

1900

17.0

67,800

49,800

4.1

16.7

71,300

4.5

4.7

072VHA

2100

20.0

76,700

55,800

4.8

16.0

80,500

 5.3 4.5

1 Rated in accordance with ISO 13256-1 – Boiler/Tower.  Cooling capacity is based on 80.6°F db, 66.2°F wb (27/19°C) entering air temperature and 86°F (30°C) entering water temperature.  Heating capacity is based on 68°F (20°C) entering air temperature and 68°F (20°C) entering water temperature. For exact dimensional data, contact your local representative for a selection.

ISO 13256-1 Performance Data - Ground Loop (Geothermal)

Unit Size

CFM 

GPM 

A-Vintage Vertical - Ground Loop (Geothermal)1

Cooling

Heating

Qt 

Qs 

kW

EER 

Qt 

kW

COP 

012VLA

400

3.5

13,700

9,300

0.8

17.4

8,200

0.9

2.8

015VLA

520

4.5

17,300

12,800

0.8

20.6

9,800

0.9

3.4

018VLA

600

5.0

22,500

16,300

1.1

20.2

12,600

1.1

3.4

024VLA

800

6.5

29,800

22,000

1.5

20.0

16,800

1.5

3.2

030VLA

1000

9.0

36,400

26,600

2.0

18.2

20,700

1.9

3.2

036VLA

1200

10.5

42,200

31,500

2.2

19.1

23,600

2.2

3.1

042VLA

1400

12.0

46,300

35,500

2.7

17.0

28,400

2.8

3.0

048VLA

1600

14.0

58,400

43,800

2.9

20.1

31,300

3.1

3.0

060VLA

1900

17.0

71,200

52,300

3.8

18.5

41,300

4.2

2.9

072VLA

2100

20.0

79,000

57,500

4.6

17.0

46,900

5.1

2.7

 1 Rated in accordance with ISO 13256-1 – Ground Loop.  Cooling capacity is based on 80.6°F db, 66.2°F wb (27/19°C) entering air temperature and 77°F (25°C) entering water temperature.  Heating capacity is based on 68°F (20°C) entering air temperature and 32°F (0°C) entering water temperature. For exact dimensional data, contact your local representative for a selection.

GPM = Gallons Per Minute, EDB = Entering Dry Bulb (ºF), EWB = Entering  Wet Bulb (ºF), EWT = Entering Water Temperature (ºF),  Qt = Capacity Total (BTUH), Qs = Capacity Sensible (BTUH), EER = Energy Efficiency Ratio, COP = Coefficient of Performance


Mammoth, Inc.
13200 Pioneer Trail
Suite 150
Eden Prairie, Minnesota 55347-4125
USA
Map & Directions

TEL: 952.358.6600
FAX: 952.358.6700
www.mammoth-inc.com