U-vintage, ceiling-hung water source heat pumps are typically installed in hallways and other corridors, away from the occupied space for reduced sound and to allow easier service access. Each single circuit unit provides heating and cooling to a specific space within the building. Mammoth offers some of the most compact horizontal water source heat pump units in the industry with critical components located to provide easy maintenance and service access in a horizontal application.
Basic Features and Benefits:
For more information, contact your local representative.
Unit Size
CFM
GPM
U Vintage Horizotal - Water Loop (Boiler/Tower)1
Cooling
Heating
Qt
Qs
kW
EER
COP
009HHU
410
2.4
9,100
7,300
0.8
12.0
11,100
0.7
4.5
013HHU
440
3.3
11,000
8,300
1.0
11.5
14,100
4.2
016HHU
550
3.8
14,200
11,400
13.6
16,900
1.1
019HHU
700
17,400
13,100
1.3
13.0
21,500
4.8
024HHU
900
6.0
26,000
20,700
1.6
16.0
29,000
1.7
5.0
030HHU
1100
8.0
30,200
24,400
2.0
15.2
33,000
036HHU
1500
9.0
37,700
30,500
2.7
14.2
38,200
2.5
4.6
043HHU
1550
44,500
33,200
3.1
14.3
47,800
2.9
052HHU
1700
14.0
48,800
36,700
14.8
49,800
3.2
062HHU
1850
59,400
41,100
65,800
1 Rated in accordance with ISO 13256-1 – Boiler/Tower. Cooling capacity is based on 80.6°F db, 66.2°F wb (27/19°C) entering air temperature and 86°F (30°C) entering water temperature. Heating capacity is based on 68°F (20°C) entering air temperature and 68°F (20°C) entering water temperature. For exact dimensional data, contact your local representative for a selection.
U Vintage Horizontal - Ground Loop (Geothermal)1
009HLU
9,800
7,600
6,500
0.6
013HLU
12,000
8,700
0.9
13.4
016HLU
14,900
11,600
16.3
019HLU
18,300
13,400
1.2
15.7
12,500
024HLU
27,400
21,200
1.5
18.0
16,800
030HLU
31,700
24,900
1.9
16.9
19,100
1.8
39,600
31,300
15.9
22,100
2.2
043HLU
48,200
34,700
2.8
17.0
28,200
2.6
052HLU
52,700
38,300
18.4
30,100
062HLU
62,800
42,600
4.0
15.6
4.3