K-vintage water-to-water units are floor-mounted in closets or small mechanical rooms and are intended to provide hot or cold water to air handler, fan coil or radiant floor heating systems within a building. In some instances, units are built into an air handler unit to conserve space while combining the efficiency of water source heat pump operation with a larger airside system.
Basic Features and Benefits:
For more information, contact your local representative.
Unit Size
SGPM
LGPM
K Vintage Water to Water - Water Loop (Boiler/Tower)1
Cooling
Heating
Qt
kW
EER
COP
064WHK
16
58,400
4.3
13.8
77,100
5.3
120WHK
33
127,700
9.0
14.1
168,100
11.8
4.2
170WHK
45
172,900
12.3
14.0
227,200
15.6
270WHK
72
257,300
18.1
14.3
338,000
23.6
360WHK
92
350,000
24.6
14.2
457,900
31.1
480WHK
120
459,500
32.2
593,100
41.0
1 Rated in accordance with ISO 13256-1 – Boiler/Tower. Cooling capacity is based on 80.6°F db, 66.2°F wb (27/19°C) entering air temperature and 86°F (30°C) entering water temperature. Heating capacity is based on 68°F (20°C) entering air temperature and 68°F (20°C) entering water temperature. For exact dimensional data, contact your local representative for a selection.
K Vintage Water to Water - Ground Loop (Geothermal)1
064WLK
59,300
3.9
15.3
45,100
4.4
3.0
120WLK
129,600
8.2
15.8
98,300
9.9
2.9
170WLK
175,400
11.2
15.7
132,800
13.1
270WLK
261,000
16.4
15.9
197,500
19.8
360WLK
355,100
22.3
267,600
26.1
480WLK
466,200
29.3
346,600
34.4
1 Rated in accordance with ISO 13256-1 – Ground Loop. Cooling capacity is based on 80.6°F db, 66.2°F wb (27/19°C) entering air temperature and 77°F (25°C) entering water temperature. Heating capacity is based on 68°F (20°C) entering air temperature and 32°F (0°C) entering water temperature. For exact dimensional data, contact your local representative for a selection.